Appendix 2: Specifications of Germany Munich 2 Data Center

Location 1km from the nearest train station and 15 minutes by car from Munich International Airport
Building Floors Two stories above ground
Seismic profile Built in non-earthquake area
Floor load limit Approximately 1,200kg/m2
Power Receiving 2 lines via different routes from different electric power substations
Capacity for critical IT load: 4.2MW
Emergency power generator N+1 redundancy; 72 hours without refuel
UPS 2N redundancy and 2N+1 also available
Battery power for 10 minutes
Air-Conditioning Equipment Water cooled; N+1 redundancy
Fire Protection N2-gas fire suppression
Supersensitive smoke detector
Security Web-based pre-application via private system
Room entry with IC cards
Surveillance cameras, lock separately
Extra-high security for financial companies
Customizable
Other Facilities Rental offices
Connectivity Carrier neutral
Certifications (both completed and planned) ISO27001 (German BSI standard)
ISO9001
ISO50001
DIN EN 50600, Class 4
Facility Rating Level TIA942* Rated-3

*US Telecommunication Industry Association (TIA) design standard for data centers. Rated-3 requires redundancy to avoid impacting IT equipment during system maintenance or malfunctions.